TeSys LUCM - unité de contrôle multifonction - classe 5..30 - 0,35..1,4A - 24Vcc"

LUCM1XBL
Image

TeSys U multifunction control unit to be inserted in advanced power bases LUB120, LUB320, LUB380 to form a TeSys U starter controller, for 1-phase motor applications up to 0.09kW@400V and 3-phase up to 0.25kW@400V. It provides full protection to motors with a rated current Ir 0.35-1.4A (Ir adjustable), overload class selectable 5-30, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). Equipped with a LCD display and a 4-button keyboard for the setting of protection and alarm parameters, and display of electrical values and events. RS485 Modbus communication RJ45 port available for remote control and integration with SoMove/MachineExpert. To be used with a 24V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base), it must be supplied with an external 24V DC power supply. Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Informations supplémentaires :

TeSys U multifunction control unit to be inserted in advanced power bases LUB120, LUB320, LUB380 to form a TeSys U starter controller, for 1-phase motor applications up to 0.09kW@400V and 3-phase up to 0.25kW@400V. It provides full protection to motors with a rated current Ir 0.35-1.4A (Ir adjustable), overload class selectable 5-30, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). Equipped with a LCD display and a 4-button keyboard for the setting of protection and alarm parameters, and display of electrical values and events. RS485 Modbus communication RJ45 port available for remote control and integration with SoMove/MachineExpert. To be used with a 24V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base), it must be supplied with an external 24V DC power supply. Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Documents à télécharger :

Résistance au choc10 gn power poles open conforming to IEC 60068-2-27 || 15 gn power poles closed conforming to IEC 60Immunité aux champs radioélectriques10 V conforming to IEC 61000-4-6
Seuil de déclenchement14.2 x Ir +/- 20 %Résistance aux vibrations2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6 || 4 gn, 5…300 Hz, power poles closed c
Résistance aux transitoires rapides2 kV class 3 serial link conforming to IEC 61000-4-4 || 4 kV class 4 all circuits except for serialImmunité aux micro-coupures3 ms
Immunité aux chutes de tension70 % / 500 ms conforming to IEC 61000-4-11Résiste aux décharges électrostatiques8 kV level 3 in open air conforming to IEC 61000-4-2 || 8 kV level 4 on contact conforming to IEC 61
Classe de surcharge thermiqueClass 5…30 50…60 Hz -13…131 °F (-25…55 °C) IEC 60947-6-2 || Class 5…30 50…60 Hz -13…131 °F (-25…55 °Code de compatibilitéLUCM